Global Switch – London North Technical Specification

Main Structural Features

  • Steel frame with concrete floors, metal faced cladding and glazing
  • Typical floor loading of 5kN/m²
  • 5m slab to slab height equating to 4.45m clear height to underside of deepest beam
  • Raised floors with anti-static tiles and a minimum height of 600mm to top of tile installed in fully fitted areas, providing minimum clear height of 3.85m to underside of deepest beam
  • Column spacing primarily based on a 6m grid

Redundant Power

  • Minimum N+1 redundancy on power supply
  • Mains power supplied via 3 x 11kV supplies for 4 transformers
  • Total available power: 9.5MVA
  • On-site diesel tanks (2 x 46,000 litres) support 50 hours at full capacity with 8 hour, and rolling 8 hour, 24x7 fuel delivery

Cooling and Environment

  • Minimum N+1 resilience on chilled water cooling system
  • Temperature and humidity in technical space to industry accepted standards and maintained within energy efficient parameters
  • Close control units (CCUs) provide conditioned air to technical space
  • Chilled water distribution pipe work throughout data centre

Fire Detection and Suppression

  • Analogue addressable fire detection system in all areas (smoke and heat) with manual break-glass units
  • High Sensitivity Smoke Detection (HSSD) devices and alarm system in the return air-flow of CCUs
  • Leak detection protection and monitoring beneath A/C unit and chilled water pipe routes
  • Gas fire suppression system using Argonite / Inergen
  • Sprinklers in landlord corridors and selected plant rooms, dry risers to all floors
  • Smoke and gas extraction

Building Management Systems

  • Dedicated 24x7 facilities management team
  • BMS system monitors M&E operation within data centre to:
    - ensure stability of the environment
    - monitor key electrical and mechanical systems
    - enable interface between key systems
    - provide data gathering

Telecommunications

  • Access to multiple telecommunications providers
  • Carrier Neutral
  • 2 dedicated Meet Me Rooms
  • Diverse cable entry points
  • Multiple cable baskets to all data risers - fully access controlled
  • Multiple connection points to each area
  • Roof space availability for satellite and antennae equipment

Security

  • Premises Controllers manage data centre security 24x7
  • Access control using photo pass cards and proximity readers
  • Intruder alarms to all areas with external infra-red barriers
  • Multiple CCTV cameras (interior and exterior)
  • Barrier controlled vehicle access and pedestrian turnstile
  • Secure managed delivery and loading area

Ancillary Services

  • Design and build services
  • Installation and cabling
  • Meeting rooms
  • On-site secure storage for deliveries
  • Technical cleaning